Municipal Ice Arena in
San Angelo, Texas

On January 22, 2004 we ran a pretest of the energy consumption of a 400 ton Chiller at a Municipal Ice Arena in San Angelo, Texas. February 9, 2004 we ran a post-test with the STEMS energy management system installed. The results are as follows:

Channel Description 1/22/04
Without STEMS
2/9/04
With STEMS

Delta as
raw data

1 Volts 283.60 282.30 -1.3
2 Amps 289.31 256.98 -32.33
5 Power Factor .87 .93 +.06
6 KVAR 40.342 26.866
-13.476

Volts x Amps x Power Factor x 1.73/1000 = 3-phase KW
283.6 x 289.31 x .87 x 1.73/1000 = 123.49 KWH
282.3 x 256.98 x .93 x 1.73/1000 = -116.71 KWH
Kilowatt Hours savings 5.78 KWH

An interesting side note:
At 7 AM on 1/22/4 the ambient temperature at this facility was 44 degrees F.
At 7 AM 0n 2/9/4 the ambient temperature at this facility was 51 Degrees F.
With higher ambient temperatures, the cooling load should have been greater on 2/9/4.